Fixed Fire Suppression



liferafts

SEA-FIRE PRE ENGINEERED NOVEC SYSTEMS

SEA-FIRE Novec NFD & NFG Fire Suppression Systems are pre-engineered and designed to protect enclosed compartments. All NFD & NFG systems operate automatically through heat activation.

SEA-FIRE NFD & NFG series extinguishers are equipped with a factory installed pressure switch which is intended for cylinder pressure supervision and may also be used to control other electrical functions (engine shutdown, air exchange equipment, etc.)

CODE & TECHNICAL DETAILS
Novec1230 fixed fire suppression  Novec 1230


liferafts

SEA-FIRE PRE ENGINEERED FM200 SYSTEMS

Sea-Fire FM 200 FD & FG Fire Suppression Systems are pre-engineered and designed to protect enclosed compartments such as Electrical Control Rooms, Machinery Compartments, Engine and Generator Compartments, Paint Lockers and Lazarettes.

Discharge will occur when the sensor valve temperature rises to the system activation point, there is also the option of manual discharge which will activate the system.

CODE & TECHNICAL DETAILS
Novec1230 fixed fire suppression  Seafire FM200


liferafts

SEA-FIRE PRE ACCESSORIES

Sea-Fire accessories include system monitor panels, heat sensor assemblies and the new generation ESRS microprocessor shutdown systems offering improved functionality and flexibility, easy installation and CAT5 plug and play connections.

All ESRE models comply with ISO marine 8846 and meet CE approval standards.

CODE & TECHNICAL DETAILS
Novec1230 fixed fire suppression  Sea-Fire Accessories


liferafts

FIREBOY Fire Extinguisher CG & MA Series - 3M Novec 1230

Fireboy has designed safe and effective engine room fire protection with no water or powdery residue.

3M Novec 1230 Fire Protection Fluid is a highly-effective clean agent fire suppressant, designed to extinguish a fire in its incipient stage before it has a chance to spread. Novec 1230 Fluid evaporates more than 50 times faster than water. It also allows the clean agent to transition from a liquid to a gaseous state very rapidly when discharged through a nozzle, and readily achieve vapor extinguishing concentrations in air. Novec 1230 fluid is a great alternative.


These systems work both as automatic and manual.

CODE & TECHNICAL DETAILS


liferafts

FIREBOY CG2 & MA2 Series -FM200 [HFC-227ea]

Since pioneering the use of Halon systems in the early 1970’s, Fireboy has designed safe and effective engine room fire protection with no water or powdery residue. All systems are heat activated to discharge the clean agent gas automatically at 175°F (79°C) with no operator intervention required. With a Fireboy system, the fire extinguishing agent is released much faster than any possible crew response, resulting in a faster fire-out time and less damage.

International system approvals (FM, USCG, CE, RINA, BV)

 

CODE & TECHNICAL DETAILS
 FM200 [HFC-227ea]


liferafts

FIREBOY Engine Shutdown Systems

Compressed gas suppressants such as HFC-227ea and 3M™ Novec™ 1230 Fire Protection Fluid will not stall a diesel engine. If a fire breaks out aboard a diesel powered vessel, the engine(s) must be shut down prior or during the discharge of the Fireboy suppression system to effectively extinguish the fire. Continued engine operation may remove the agent, lowering the concentration required to effectively extinguish the fire, making an Engine Shutdown System necessary.

ESC, ELS and ES Series

 

CODE & TECHNICAL DETAILS


liferafts

Engineered Systems in NOVEC 1230 and FM200

Systems to protect from 40m³ to 3000 m³ SOLAS and MED Approved for Commercial Ships and Yachts.

Custom designed and manufactured to order.

We will also submit the system for approval by the relevant authorities and/or class societies, when required.